In electrical engineering, three-phase electric power systems have at least three conductors carrying alternating current voltages that are offset in time by one-third of the period. A three-phase system may be arranged in delta (∆) or star (Y) (also denoted as wye in some areas). A wye system allows the use of two different voltages from all three phases, such as a 230/400V system which provides 230V between the neutral (centre hub) and any one of the phases, and 400V across any two phases. A delta system arrangement only provides one voltage magnitude, however it has a greater redundancy as it may continue to operate normally with one of the three supply windings offline, albeit at 57.7% of total capacity.[1] Harmonic currents in the neutral may become very large if non-linear loads are connected.

Definitions

Elementary six-wire three-phase alternator, with each phase using a separate pair of transmission wires no.
Elementary three-wire three-phase alternator, showing how the phases can share only three transmission wires.
Three-phase transformer. Each phase has its own pair of windings

In a star (wye) connected topology, with rotation sequence L1 - L2 - L3, the time-varying instantaneous voltages can be calculated for each phase A,C,B respectively by:

VL1N=sin(θ)*VP
VL2N=sin(θ23π)*VP=sin(θ+43π)*VP
VL3N=sin(θ43π)*VP=sin(θ+23π)*VP

where:

VP is the peak voltage,
θ=2πft is the phase angle in radians
t is the time in seconds
f is the frequency in cycles per second and
voltages L1-N, L2-N and L3-N are referenced to the star connection point.

Balanced loads

Generally, in electric power systems, the loads are distributed as evenly as is practical between the phases. It is usual practice to discuss a balanced system first and then describe the effects of unbalanced systems as deviations from the elementary case.

Constant power transfer

An important property of three-phase power is that the power available to a resistive load, P=VI=1RV2, is constant at all times.

PLi=VLi2RPTOT=iPLi

To simplify the mathematics, we define a nondimensionalized power for intermediate calculations, p=1VP2PTOTR

p=sin2θ+sin2(θ23π)+sin2(θ43π)=32

Hence (substituting back):

PTOT=3VP22R

since we have eliminated θ we can see that the total power does not vary with time. This is essential for keeping large generators and motors running smoothly. Actually, the load need not be resistive for achieving a constant instantaneous power since, as long as it is balanced or the same for all phases, it may be written as

Z=|Z|ejφ

so that the peak current is

IP=VP|Z|

for all phases and the instantaneous currents are

IL1=IPsin(θφ)
IL2=IPsin(θ23πφ)
IL3=IPsin(θ43πφ)

Now the instantaneous powers in the phases are

PL1=VL1IL1=VPIPsin(θ)sin(θφ)
PL2=VL2IL2=VPIPsin(θ23π)sin(θ23πφ)
PL3=VL3IL3=VPIPsin(θ43π)sin(θ43πφ)

Using angle subtraction formulae:

PL1=VPIP2[cosφcos(2θφ)]
PL2=VPIP2[cosφcos(2θ43πφ)]
PL3=VPIP2[cosφcos(2θ83πφ)]

which add up for a total instantaneous power

PTOT=VPIP2{3cosφ[cos(2θφ)+cos(2θ43πφ)+cos(2θ83πφ)]}

Since the three terms enclosed in square brackets are a three-phase system, they add up to zero and the total power becomes

PTOT=3VPIP2cosφ

or

PTOT=3VP22|Z|cosφ

No neutral current

For the case of equal loads on each of three phases, no net current flows in the neutral. The neutral current is the inverted vector sum of the line currents. See Kirchhoff's circuit laws.

IL1=VL1NR,IL2=VL2NR,IL3=VL3NRIN=IL1+IL2+IL3

We define a non-dimensionalized current, i=INRVP:

i=sinθ+sin(θ2π3)+sin(θ+2π3)=sinθ+2sinθcos2π3=sinθsinθ=0

Since we have shown that the neutral current is zero we can see that removing the neutral core will have no effect on the circuit, provided the system is balanced. Such connections are generally used only when the load on the three phases is part of the same piece of equipment (for example a three-phase motor), as otherwise switching loads and slight imbalances would cause large voltage fluctuations.

Unbalanced systems

In practice, systems rarely have perfectly balanced loads, currents, voltages and impedances in all three phases. The analysis of unbalanced cases is greatly simplified by the use of the techniques of symmetrical components. An unbalanced system is analysed as the superposition of three balanced systems, each with the positive, negative or zero sequence of balanced voltages.

When specifying wiring sizes in a three-phase system, we only need to know the magnitude of the phase and neutral currents. The neutral current can be determined by adding the three phase currents together as complex numbers and then converting from rectangular to polar co-ordinates. If the three phase RMS (Root Mean Square) currents are IL1, IL2 and IL3, the neutral RMS current is:

IL1+IL2*cos23π+j*IL2*sin23π+IL3*cos43π+j*IL3*sin43π

which resolves to

IL1IL2*0.5IL3*0.5+j*32*(IL2IL3)

The polar magnitude of this is the square root of the sum of the squares of the real and imaginary parts, which reduces to

IL12+IL22+IL32IL1*IL2IL1*IL3IL2*IL3[2]

Non-linear loads

With linear loads, the neutral only carries the current due to imbalance between the phases. Devices that utilize rectifier-capacitor front end such as switch-mode power supplies, computers, office equipment and such produce third order harmonics. 3rd, current are in-phase on all the supply phases. Third harmonics add up in neutral which can cause the neutral current in a wye system to exceed the phase current.[3][4]

Revolving magnetic field

Any polyphase system, by virtue of the time displacement of the currents in the phases, makes it possible to easily generate a magnetic field that revolves at the line frequency. Such a revolving magnetic field makes polyphase induction motors possible. Indeed, where induction motors must run on single-phase power (such as is usually distributed in homes), the motor must contain some mechanism to produce a revolving field, otherwise the motor cannot generate any stand-still torque and will not start. The field produced by a single-phase winding can provide energy to a motor already rotating, but without auxiliary mechanisms the motor will not accelerate from a stop when energized.

A rotating magnetic field of steady amplitude requires that all three phase currents be equal in magnitude, and accurately displaced one-third of a cycle in phase. Unbalanced operation results in undesirable effects on motors and generators.

Conversion to other phase systems

Provided two voltage waveforms have at least some relative displacement on the time axis, other than a multiple of a half-cycle, any other polyphase set of voltages can be obtained by an array of passive transformers. Such arrays will evenly balance the polyphase load between the phases of the source system. For example, balanced two-phase power can be obtained from a three-phase network by using two specially constructed transformers, with taps at 50% and 86.6% of the primary voltage. This Scott T connection produces a true two-phase system with 90° time difference between the phases. Another example is the generation of higher-phase-order systems for large rectifier systems, to produce a smoother DC output and to reduce the harmonic currents in the supply.

When three-phase is needed but only single-phase is readily available from the electricity supplier, a phase converter can be used to generate three-phase power from the single phase supply.

System measurements

It is possible to measure the power in a three-phase system using two transducers when there is no neutral, or three transducers when there is neutral.[5] Blondel's theorem states that the number of measurement elements required is one less than the number of current-carrying conductors.[6]

See also

References

43 year old Petroleum Engineer Harry from Deep River, usually spends time with hobbies and interests like renting movies, property developers in singapore new condominium and vehicle racing. Constantly enjoys going to destinations like Camino Real de Tierra Adentro.

  • 20 year-old Real Estate Agent Rusty from Saint-Paul, has hobbies and interests which includes monopoly, property developers in singapore and poker. Will soon undertake a contiki trip that may include going to the Lower Valley of the Omo.

    My blog: http://www.primaboinca.com/view_profile.php?userid=5889534

ar:تيار ثلاثي الأطوار ca:Sistema trifàsic da:Vekselspænding (3-faset) de:Dreiphasenwechselstrom et:Kolmefaasiline toitesüsteem es:Sistema trifásico fr:Triphasé hr:Trofazna struja it:Sistema trifase ms:Bekalan elektrik tiga fasa nl:Krachtstroom ja:三相交流 pl:Układ trójfazowy pt:Sistema trifásico ru:Трёхфазная система электроснабжения fi:Kolmivaihevirta sv:Trefassystem ta:முத்தறுவாய் மின்திறன்

  1. http://www.ibiblio.org/kuphaldt/socratic/output/deltawye_instructor.pdf public domain
  2. 20 year-old Real Estate Agent Rusty from Saint-Paul, has hobbies and interests which includes monopoly, property developers in singapore and poker. Will soon undertake a contiki trip that may include going to the Lower Valley of the Omo.

    My blog: http://www.primaboinca.com/view_profile.php?userid=5889534
  3. Template:Cite web
  4. Template:Cite web
  5. Template:Cite web
  6. Template:Cite web